At a glance
- Area limit per fire guard
- 50,000 square feet
- Patrol frequency
- Every affected area at least once an hour
- Record retention
- At least 3 years on premises
- After fire watch ends
- Records maintained at least 48 hours
Who may stand fire watch
A fire watch is required whenever a required fire protection system is out of service. During the first 4 hours, in an area of no more than 50,000 square feet, the impairment coordinator can do it. So can a trained, knowledgeable person the owner designates.
After 4 hours, only F-01 holders may perform the fire watch.
New York
Certificate of Fitness F-01 -- Fire Guard for Impairment (Citywide)
$79Your one-time purchase includes 90 days of access from the time payment clears. No subscription. No automatic renewal
- Prepared scope and limits shown clearly
- Targeted practice by weak area
- Worked answer explanations
- Missed-question and due-review queues
- 90 days of access
Patrol rules
One fire guard may cover no more than 50,000 square feet. Larger areas need an additional F-01 holder for each 50,000 square feet. Every affected area must be patrolled at least once an hour.
Fire guards stay on duty around the clock until the systems are restored, and they cannot be given other jobs. Patrols include checking exits, doors, exit signs and lighting, ignition sources, smoking and garbage.
The daily record
The log must show inspections completed, defects found and violations found. It must also include the date, the fire guard's name, certificate number and signature.
Records stay on the premises for at least 3 years. They must also be maintained for at least 48 hours after the fire watch ends.
Notifying FDNY of an impairment
FDNY must be told whenever a standpipe system is out of service, for any length of time.
For sprinklers or fire alarms, notification is needed in four cases: the system is out on more than one floor; sprinkler repairs will take longer than 8 hours; fire alarm repairs will keep it down more than 8 hours in a 24-hour period; or another system in the area is also out.
If you discover a fire
Call 911 first, and sound the pull station if there is one. A pull station may not send a signal to FDNY, so the phone call is always needed. Only after calling 911 do you notify the impairment coordinator or other responsible person.
Give the nature of the emergency and the address, since those are the most critical details. Evacuate the fire floor and the floor above first, using the stairs, not the elevator.
Sources
More on the FDNY Fire Guard (F-01)
- What is on the FDNY F-01 Fire Guard for Impairment exam?
- What does FDNY not publish about the F-01 exam?
- What score do I need to pass the FDNY F-01, and what if I fail?
- Does RankHigh cover the pictures and phone numbers in the F-01 booklet?
- What does the lithium-ion battery part of the FDNY F-01 exam cover?
- What are the construction-site rules and Appendix A tables on the FDNY F-01?